Smart-UPS Rack (VA): 450, 500, 700, 750, 1000, 1400, 1500, 2000, 2200, 3000, 5000
Download the Full Operation and Troubleshooting Quick Guide for Smart UPS Rack Mount Here
Step 1 Connect the UPS’s Internal batteries (Figure 1):
NOTE: The Battery Disconnect/Connector may vary or be omitted on some models. Figure 1 illustrates some of the variations in connectors. Please follow the illustration which best resembles your UPS.
Procedure for Figure 1: (1, 2, 3, 4)
- 1.1 Remove the Front Bezel (1)
- 1.2 Locate the battery connector which will be adjacent to the battery compartment. Connect the Battery connector to the UPS connector. A snap will be felt as the connector partially engages the jack. A second snap will be felt as the connector securely seats in the Battery Jack (2)
- 1.3 Replace the front Bezel.
AND / OR
Procedure for Figure 1: (A)
- 1.1 Locate the ‘Battery Disconnect’ or ‘Battery Connector’ on the rear panel of the UPS. It is typically a Yellow connector.
- 1.2 If the Battery Disconnect/Connector has a metal cover, remove the fastening screws and move the cover (A)
- 1.3 Connect the battery by pressing the yellow connector into the Battery Jack. A snap will be felt as the connector partially engages the jack. A second snap will be felt as the connector securely seats in the Battery Jack
Step 2 Install UPS accessories (Figure 2):
NOTE: Ensure the UPS is turned off prior to installing any accessories. Some accessories are not provided with the UPS, please contact APC or CBM for the compatible accessories.
- 2.1 Install SmartSlot accessory (if applicable) (1)
- 2.2 Install Step-down transformer (if applicable).
- 2.3 Install all external Battery Packs (if applicable). The External Battery Pack connector is located on the rear panel of the UPS, and is either BLUE/RED (48V) or GREY (24V) If the External Battery Pack Connector has a metal cover, remove the fastening screws and move the cover as in Figure 1.A.(2)
Step 3 Connect wiring & charge UPS (Figure 3):
NOTE: Ensure equipment is turned off.
- 3.1 Connect equipment to UPS 1
- 3.2 Connect UPS Power Cord to a suitable power receptacle 2
- 3.3 Set UPS circuit breakers to the ‘ON’ position (if applicable) 3
- 3.4 Power-up the UPS by pressing the test button
- 3.5 Wait for the Self-Test to complete, then Power-up equipment.
- 3.6 Allow UPS to charge batteries for 24 hours prior to operating on battery or performing additional Self-Test or Calibration tests.
UPS Front Panel (Figure 4):
NOTE: Symbols & functions may differ on some UPS models. Figure 4 illustrates some of the variations in displays. Please use the illustration which best resembles your UPS.
UPS Back Panel (Figure 5):
NOTE: Panel layout may differ on some models.
UPS Troubleshooting:
Return to the Operation Guide
NOTE: Troubleshooting procedures may differ depending on UPS model
Back-UPS (Plastic) Troubleshooting
UPS will not turn on:
- Problem: ON button not pushed. Solution: Press the ON button once to power the UPS and the load.
- Problem: UPS not connected to AC power supply. Solution: Check that the power cable from the UPS to the power supply is securely connected at both ends.
- Problem: UPS input circuit breaker tripped. Solution: Reduce the load on the UPS by unplugging equipment and reset the circuit breaker (on back of UPS) by pressing the plunger back in.
- Problem: Very low or no utility voltage. Solution: Check the AC power supply to the UPS with a table lamp. If the light is very dim, have the utility voltage checked.
- Problem: Battery not connected properly. Solution: Confirm the battery connections.
UPS will not turn off:
- Problem: Internal UPS fault. Solution: Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
UPS operates on-battery although normal line voltage exists:
- Problem: UPS’s input circuit breaker tripped. Solution: Reduce the load on the UPS by unplugging equipment and reset the circuit
breaker (on back of UPS) by pressing the plunger back in. - Problem: Very high, low, or distorted line voltage. Inexpensive fuel powered generators can distort the voltage. Solution: Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the load, reduce the UPS’s sensitivity. See User’s Manual for procedures.
UPS beeps occasionally
- Problem: Normal UPS operation. Solution: None. The UPS is protecting the load
UPS does not provide expected backup time:
- Problem: The UPS’s battery is weak due to recent outage or is near the end of its service life. Solution: Charge the battery. Batteries require recharging after extended outages. Also, they wear faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet lit.
- Problem: The UPS is overloaded. Solution: Check the UPS’s load display. Unplug less needed equipment, such as printers.
Front panel indicators flash sequentially:
- Problem: The UPS has been shut down by remote control. Solution: None. The UPS will restart automatically when utility power returns.
All indicators are lit and UPS emits a constant beeping:
- Problem: Internal UPS fault. Solution: Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.
All indicators are off and UPS is plugged into wall outlet:
- Problem: The UPS is shut down and the battery is discharged from an extended outage. Solution: None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.
The replace battery light is lit:
- Problem: Weak batteries. Solution: Do another self-test to see if it clears.
- Problem: Replacement batteries not connected properly. Solution: Confirm the battery connections.